Abstract:
In worldwide reinforced concrete is the major construction material used for buildings and
general structures. The requirement of strengthening of reinforced concrete structures may
emerge not only due to timed degradation but also due to various reasons like construction
faults, increased loads and changes in utilization purpose etc. Rehabilitation of reinforced
concrete structures using Carbon Fiber Reinforced Polymer materials is recognized as a very
effective retrofitting method in all over the world and provides advantages like durability,
water proofing capability, ease of application due to less weight etc. CFRP materials can be
used for strengthening of almost all the components of a RC structure like beams, slabs
columns, beam column joints etc. Among these, strengthening of columns should be done
with greater care because of failure of a major column may lead to failure of complete
structure. In this research attention was given to study the behavior of short RC columns
strengthened with CFRP composites.
The current practice on strengthening reinforced concrete columns with external CFRP
jacketing is to provide full confinement all over the column with less care on the required
strength increment. As CFRP is a costly material providing partial confinement where
necessary may be a viable option for cost reduction, rather than providing full confinement.
The numbers of studies that have been carried out on partially confined rectangular columns
are relatively less and only some available design guidelines provide design process for
providing partial confinement using CFRP.
It is obvious that the best way to identify the structural behavior is through a thorough
experimental study. But behaviour CFRP confined columns depends on many parameters
such as, failure stresses and strains of CFRP jacket, jacket thickness, number of CFRP layers,
percentage of steel reinforcement etc. Studying of all those parameters experimentally is not
a cost effective option as the structural form and load sharing will be specific for a single
case. Finite element modeling is the best way to study a criterion that depends on this kind of
large number of input variables. But still the finite element modeling of confined concrete
column is in evolving stage and there is no globally accepted finite element model to predict
the behavior of CFRP confined columns.
The experimental and theoretical studies available in Sri Lanka regarding CFRP
strengthening are next to zero. When design guidelines available for CFRP design are
considered, there are various design codes for different countries like USA, Japan, Canada
and Switzerland. Under this background designers and contractors in Sri Lanka are in a fuzz
regarding which design guideline system will provide adequate safety factor while maintain
the feasibility of the project
Three major objectives were setup under this study. An experimental study was carried out to
investigate the ductility and ultimate load carrying capacity increment of both reinforced and
unreinforced square columns due to full confinement and to understand the behaviour of
reinforced concrete columns with partial confinement. Second objective was to develop a
finite element model using ANSYS software to simulate the behavior of confined concrete
columns and study an analytical model capable of predicting stress strain behaviour and
ultimate load carrying capacity of CFRP confined columns. Also a study was carried out
about different available guidelines and attempt was made to identify the factor of safety
provided for each design methods against obtained experimental results.
Under experimental study total number of 17 columns with dimensions of 150 150 350
mm was tested. The test specimens consist of 6 plain concrete columns with 3 control specimens and 3 fully confined columns. 11 reinforced concrete columns with 3 control
specimens, 3 columns with full confinement and 5 columns with partial confinement. Two
wrapping patterns were used for partially confined columns, three specimens with two sets of
75mm width wraps at top and bottom of the column and two specimens with three 50mm
wraps at top bottom and middle of the column. The volumetric ratio of CFRP for partially
confined column specimens were kept constant to study the effect of wrapping pattern and
jacket location for strength and ductility increment. All the columns were tested for axial
compression. Under analytical study the model proposed by “Harajli” was studied. CFRP
design specifications published by American Concrete Institute (ACI) and International
Federation for structural concrete (fib), Switzerland were reviewed against the experimental
results to identify the factor of safety against ultimate load carrying capacity estimation.
The results of experimental study revealed that any kind of external confinement, full or
partial with external CFRP jacketing is capable of increasing the load carrying capacity and
ductility of a column to a considerable extent. The load carrying capacity increment for fully
wrapped reinforced concrete columns were 100% while for plain concrete columns it was
47%. When load carrying capacity increment of partially confined columns considered, the
specimens with two 75mm wraps showed a capacity increment of 59% while specimens with
three 50mm wraps showed an increment of 83%. From above observation it was realized that
for partially confined columns not only the volumetric ratio of the CFRP wrapping but also
the wrapping pattern have a large influence on load carrying capacity. When ductility
increment is considered it was observed that ductility increment is proportional to the
strength increment, more the strength increment more the ductility increment.
The finite element model based on Extended Drucker Prager plasticity model for concrete
showed a good prediction of horizontal strain vs. vertical stress variation for fully confined
models and could predict the failure load with an error of 1.8% hence the developed finite
element model can be treated as an acceptable model.
The analytical model proposed by Harajli showed a considerable variation of stress strain
behaviour prediction but the ultimate failure load prediction according to above analytical
model showed a good agreement with experimental failure loads with an error of 1.1%
The estimated failure loads from ACI guidelines showed a factor of safety of 3.5 against
experimental results while fib guidelines showed a factor of safety of 1.6 for fully confined
reinforced concrete specimens. Only fib guidelines gives a method to estimate failure load of
partially confined columns and showed a factor of safety of 2 for specimens with 75mm
wrappings and 2.1 for specimens with 50mm wrappings. As the current practice is to provide
full confinement for columns and two guidelines shows a considerable variation of factor of
safety the designers are advised to select the suitable design system based on the risk level
associated with a specific project.
Keywords: CFRP, reinforced concrete columns, partial confinement, strength,
ductility, finite element modeling