Show simple item record

dc.contributor.advisor Perera, R
dc.contributor.author Weerasekara, CH
dc.date.accessioned 2015-09-16T09:30:33Z
dc.date.available 2015-09-16T09:30:33Z
dc.date.issued 2015-09-16
dc.identifier.uri http://dl.lib.mrt.ac.lk/handle/123/11352
dc.description.abstract Power distribution systems feed in radial and ring feeding mechanisms. The radial feeding arrangement is used in rural networks where reliability is very low. In urban areas, ring feeding arrangements are likely to be used which provides an alternative feeding arrangement for load. Colombo City uses an open loop feeding arrangement with a normally open point in the ring arrangement. It has an underground 11kV network where panel substations in a ring (partly meshed) manner are connected around the primary substation. Outgoing feeders from these panel substations are again connected in a ring manner through Ring Main Units. By providing correct directional protection coordination these panel substations can be operated in a closed loop ring arrangement to improve reliability. It will also reduce distribution line losses and improve the system voltage profile. In my dissertation, area fed by Primary Substation F was taken into consideration for analysis. Different time zones were recognized based on load changes for week days and weekends. The possible ring arrangements were identified and load flow analysis was carried out using SynerGEE for radial and closed loop ring arrangement to detail the power loss reduction, voltage improvement, excessive active power and reactive power absorbed by loads. Reliability improvement was derived for SAIFI and SAIDI, using the rate of failure of cables based on the cable failure details of Colombo City. Voltage analysis and cost analysis were also carried out using SynerGEE. Directional protection coordination was derived for two feeders operating in closed loop, two substations operating in closed loop and three substations operating in closed loop to cover the identified paralleling patterns in selected zones. Based on fault levels and the cable impedance data protection settings were calculated for actual field conditions for each pattern. Each pattern was simulated in Matlab to monitor the voltage and current variations for cable faults. In conclusion, if the conditions prevail, the panel arrangement existing in Colombo City provides an easy approach to operate the system in a closed loop ring arrangement by replacing existing numerical relays with directional numerical relays, which improves the reliability, reduces the distribution losses and provides voltage improvements. en_US
dc.language.iso en en_US
dc.subject MSc in Electrical Engineering
dc.subject ELECTRICAL ENGINEERING-Dissertation
dc.subject POWER DISTRIBUTION NETWORK
dc.subject POWER DISTRIBUTION NETWORK-Colombo City
dc.title System improvement through cordinated ring circuit in medium en_US
dc.type Thesis-Full-text en_US
dc.identifier.faculty Engineering en_US
dc.identifier.degree MSc in Electrical Engineering en_US
dc.identifier.department Department of Electrical Engineering en_US
dc.date.accept 2015
dc.identifier.accno 108989 en_US


Files in this item

This item appears in the following Collection(s)

Show simple item record