Institutional-Repository, University of Moratuwa.  

Analysis of transient overvoltage in medium voltage distribution network of Ceylon Electricity Board

Show simple item record

dc.contributor.advisor Lucas, JR
dc.contributor.advisor Banda, HMW
dc.contributor.author Weerawardena, WAV
dc.date.accessioned 2011-07-14T07:10:12Z
dc.date.available 2011-07-14T07:10:12Z
dc.identifier.citation Weerawardena, W.A.V. (2010). Analysis of transient overvoltage in medium voltage distribution network of Ceylon Electricity Board [Master's theses, University of Moratuwa]. Institutional Repository University of Moratuwa. http://dl.lib.mrt.ac.lk/handle/123/1622
dc.identifier.uri http://dl.lib.mrt.ac.lk/handle/123/1622
dc.description.abstract This thesis presents the analysis of transient overvoltages in medium voltage (33kV) network and the research is based on feeder lines in the Uva province. Parameters which influence lightning performance of overhead distribution lines such as line height, line length, type of structure, availability of shield wire and flash density in the area are discussed in details. More over, failures due to transient overvoltages and its impact on the reliability of the network are analyzed in this study. Lightning may cause flashovers from direct strokes or induced voltage from nearby strokes. Direct lightning to power distribution lines causes insulation flashovers in great majority of the cases. Therefore the goal of this research is to estimate the lightning performance level of feeder lines and investigate improvements. Shielding effect from nearby trees, critical flashover voltages for different flashover paths and deterioration of insulation with aging are also discussed. Thus the analysis of lightning related incidents such as transformer failures, arrester failures and nuisance fuse blows are presented. The study of transformer installation reveals that arrester lead length becomes critical during a lightning discharge since it generates high voltage stress in the winding which may fail the distribution transformer. Earth rod impulse resistance is also an important parameter which increases the voltage stress. It is necessary to develop models, using, electrical parameters for simulation of transient overvoltages. The PSCAD software is especially developed to study transient simulations of power systems. Variation of transient overvoltages due to strikes to phase wires, strikes to earth wire, and variation due to striking distance are discussed in this study. Further, simulation of surge arrester performance and nuisance fuse blows are also presented. Finally, the study presents applications to achieve zero lead length in substation, introduction of surge durable fuses and procedures which can be implemented to improve lightning performance in the MV network.
dc.language.iso en en_US
dc.subject ELECTRICAL ENGINEERING - Dissertation
dc.subject ELECTRIC POWER DISTRIBUTION
dc.subject LIGHTNING
dc.subject LIGHTNING PROTECTION
dc.subject ELECTRIC LINES
dc.title Analysis of transient overvoltage in medium voltage distribution network of Ceylon Electricity Board
dc.type Thesis-Full-text
dc.identifier.faculty Engineering en_US
dc.identifier.degree MSc en_US
dc.identifier.department Department of Electrical Engineering en_US
dc.date.accept 2010
dc.identifier.accno 94847 en_US


Files in this item

This item appears in the following Collection(s)

Show simple item record