Show simple item record

dc.contributor.advisor Perera, HYR
dc.contributor.author Weeratunga, SMMS
dc.date.accessioned 2011-07-19T10:29:51Z
dc.date.available 2011-07-19T10:29:51Z
dc.identifier.citation Weeratunga, S.M.M.S. (2009). Effective fault isolation methods to improve 33kV network reliability [Master's theses, University of Moratuwa]. Institutional Repository University of Moratuwa. http://dl.lib.mrt.ac.lk/handle/123/1751
dc.identifier.uri http://dl.lib.mrt.ac.lk/handle/123/1751
dc.description.abstract Improving reliability in power system is very important to the utilities as well as to the country as it is an important attribute of the supply quality and increases the end user satisfaction. The aim of this study is to investigate the fault identification and isolation techniques to improve reliability. This study focuses on the following; 1. Reliability status of 33kV network of C.E.B. 2. Type of faults in 33kV network and outage reduction methods. 3. Develop a mathematical model for reliability evaluation. 4. Analyze protection scheme of C.E.B 33kV network. 5. Design new protection scheme to reduce outages. The analyzed reliability indices of C.E.B are far below compared to internationally Accepted levels. In this study reliability status of 33kV network is analyzed using event log data of reclosers and breakdown reports of Consumer Service Centers. The author is working atRegion-04, C.E.B and two switching gantries of Region-04 are selected to analyze events one in wet zone and other in coastal zone. It can be seen that outage time and fault frequency are high during both monsoon periods,86% of faults are tine to earth, 67% of faults are of transient nature and the repair time in case of overcurrent fault is high due to poor workmanship in line connections. With this study predominant causes of faults in the network can be identified by using event log of recloser. The several methods for outage reduction are identified, installation of fault indicators for remote indication and remote operation of reclosers, using line sectionalize devices. The protection scheme of 33kV network is analyzed to find techniques to reduce outages. The downstream protective devices (fuse on Spurs) beyond the recloser do not distinguish permanent and transient faults. It can be seen nuisance fuse blowing in spurs as well as nuisance recloser lockout affecting all customers in feeder. A new protection scheme is designed to overcome the above problems. The developed method isolates unhealthy spurs from healthy sections, improves reliability and reduces maintenance cost and extent of unserved energy.
dc.language.iso en en_US
dc.subject ELECTRICAL ENGINEERING - Dissertation
dc.subject ELECTRIC POWER SYSTEMS - Reliability
dc.subject ELECTRIC POWER SYSTEMS - Fault Location
dc.title Effective fault isolation methods to improve 33kV network reliability
dc.type Thesis-Full-text
dc.identifier.faculty Engineering en_US
dc.identifier.degree MSc en_US
dc.identifier.department Department of Electrical Engineering en_US
dc.date.accept 2009
dc.identifier.accno 92963 en_US


Files in this item

This item appears in the following Collection(s)

Show simple item record