dc.contributor.advisor |
Wijayapala, WDAS |
|
dc.contributor.advisor |
Udawatta, L |
|
dc.contributor.advisor |
Shanthi, KPK |
|
dc.contributor.author |
Sellahannadi, JR |
|
dc.date.accessioned |
2011-07-22T10:59:16Z |
|
dc.date.available |
2011-07-22T10:59:16Z |
|
dc.identifier.citation |
Sellahannadi, J.R. (2010). Development of a neuro-fuzzy system for condition monitoring of power transformers [Master's theses, University of Moratuwa]. Institutional Repository University of Moratuwa. http://dl.lib.mrt.ac.lk/handle/123/1905 |
|
dc.identifier.uri |
http://dl.lib.mrt.ac.lk/handle/123/1905 |
|
dc.description.abstract |
Well-being of Power Transformers is crucial to the reliable operation of a Power System. They represent a high capital investment in a Transmission Substation while being a key element determining the loading capability of the station within the network. With appropriate maintenance, including insulation reconditioning at the appropriate time, the technical life of a transformer can be extended. Assessment of Power Transformer condition is very important to maintenance engineers on the way
to diagnose incipient faults and implementation of necessary maintenance plans to prolong their life span. Therefore different testing methods and diagnosis techniques
are used for condition assessment of transformers; namely Dissolved Gas Analysis (DGA), moisture content measuring tests in oil/paper, Insulation Resistance (IR) measurement, acidity in oil etc. Accuracy of the final conclusion depends on the experience and knowledge of the maintenance engineer and the data which he referred to. Therefore, it is appropriate to have an Expert System, as a guide to maintenance engineers in the Ceylon Electricity Board (CEB), so as to address the above problems.
This thesis describes the degradation of insulation, ageing process, faults and testing
methods of transformers. Much attention was paid to DGA as a diagnosis tool. This thesis introduces two computer based expert systems to analyze the results from various diagnosis techniques and tests which are used in CEB at present. First program was written on Visual Basic environment and included essential tests including DGA which are carried out by CEB for its transformers. Knowledge base for this program was developed by using various standards, text books, transformer manufacturers' recommendations and the opinions of my supervisors and experienced engineers. Twenty Five (25) numbers of DGA test results of transformers were analyzed by using this program and such transformers were grouped according to the IEEE standards. Limitations of conventional DGA methods with frequent non decisions can be addressed by fuzzy-logic based diagnosis for power transformer incipient faults. Therefore, the second program was developed to
meet the above demand by using Adaptive Neuro-Fuzzy Inference System (ANFIS) in MATLAB Environment. The developed ANFIS-based diagnosis system provides further improvement to fuzzy-logic based techniques by providing auto-learning capabilities. This program was tested for faults with 30 DGA test results and the outcome is within the satisfactory level. |
|
dc.language.iso |
en |
en_US |
dc.subject |
ELECTRICAL ENGINEERING - Thesis |
|
dc.subject |
ELECTRIC POWER DISTRIBUTION |
|
dc.subject |
TRANSFORMERS |
|
dc.subject |
ARTIFICIAL INTELLIGENCE - Applications |
|
dc.subject |
NEURAL NETWORKS - Applications |
|
dc.subject |
EXPERT SYSTEMS - Applications |
|
dc.title |
Development of a neuro-fuzzy system for condition monitoring of power transformers |
|
dc.type |
Thesis-Abstract |
|
dc.identifier.faculty |
Engineering |
en_US |
dc.identifier.degree |
MSc |
en_US |
dc.identifier.department |
Department of Electrical Engineering |
en_US |
dc.date.accept |
2010 |
|
dc.identifier.accno |
94540 |
en_US |