Study for effective lighting protection system for floating roof tanks in petroleum refinery

dc.contributor.advisorLucas JR
dc.contributor.advisorRodrigo A
dc.contributor.authorBamunuarachchi BAT
dc.date.accept2020
dc.date.accessioned2020
dc.date.available2020
dc.date.issued2020
dc.description.abstractRefinery is considered as the foremost division of the Ceylon petroleum corporation which ensures the safety of the operation of process plant as well as for maintaining the required country’s demand for petroleum products to enhance the energy sector of the country. Since the un-interruptible continuous refinery operation is critically important to maintain national requirement of petroleum product and protecting the tanks and process equipment is essential. In this study, main concern about floating roof large crude oil storage tank facility. The most general method to prevent the possible damage to floating roof crude oil storage tank is using good earthing. The earthing system provides an electrical path to the ground and performance of the earthing system gets better as the earth loop impedance becomes lower. Since it is among the major concerns currently Refinery engineering staff is struggling with; and a proper method for reducing the sparks due to lightning mainly at critical locations were studied and simulations were done by using the floating roof tank model prepared by using PSCAD software which was validated with the actual model tank tested in the UOM laboratory. Direct and In-direct surge currents were calculated theoretically for 25 kA, 50 kA, 100 kA and 200 kA surges of 10/350 μS & 8/20 μS by applying calculated surge currents to the tank model. Finally, by analyzing all the results and the protection methods of different types of grounding devices were studied and proposed adjustable grounding conductor (AGC) with suitable locations as the optimum solution.en_US
dc.identifier.accnoTH4216en_US
dc.identifier.degreeMSc in Electrical Installationsen_US
dc.identifier.departmentDepartment of Electrical Engineeringen_US
dc.identifier.facultyEngineeringen_US
dc.identifier.urihttp://dl.lib.uom.lk/handle/123/16468
dc.language.isoenen_US
dc.subjectELRCTRICAL ENGINEERING-Dissertationsen_US
dc.subjectELECTRICAL INSTALLATION-Dissertationsen_US
dc.subjectELECTRIC GROUNDINGen_US
dc.subjectLIGHTNING PROTECTIONen_US
dc.subjectPETROLIUM REFINERIES-Lightning Protectionen_US
dc.subjectCOMPUTER SIMULATIONSen_US
dc.subjectCOMPUTER SOFTWARE-PSCAD Softwareen_US
dc.titleStudy for effective lighting protection system for floating roof tanks in petroleum refineryen_US
dc.typeThesis-Full-texten_US