Potential energy saving with high ΔT chilled water designs compared to the conventional low ΔT designs for office buildings in hot and humid climates

dc.contributor.authorJoseph, AI
dc.contributor.authorWijewardane, MA
dc.date.accessioned2026-07-23T04:33:11Z
dc.date.issued2024
dc.description.abstractThis study investigates the potential energy-saving benefits associated with high delta-T (ΔT) chilled water designs compared to the conventional low delta-T (ΔT) designs in office buildings in hot and humid climates. High ΔT systems operates with higher temperature difference between supply and return chilled water temperatures compared to conventional low ΔT systems. This high ΔT requirement is specified in the ASHRAE 90.1: 2016 under subsection 6.5.4. “Chilled Water coil selection and theoretical background of temperature difference towards energy efficiency”. Hence, the aim of the study is to evaluate the capital cost reduction and annual energy savings achievable through the implementation of high ΔT configurations and to evaluate the applicability of this configuration in hot and humid countries. The study followed a comprehensive research methodology that involved analyzing 03 chilled water ΔT options and assessing their impact on capital costs and energy consumption. The findings of the study demonstrate significant cost savings and energy efficiencies associated with high ΔT chilled water designs. A capital cost reduction of 2.8% in the ΔT=7°C system and 3.6% in the ΔT=8.3°C systems were observed compared to the conventional ΔT=5°C system. Additionally, the annual energy analysis revealed a 0.97% reduction of energy costs in the ΔT=7°C system and a higher energy cost saving of 1.93% in the ΔT=8.3°C system compared to the ΔT=5°C system. These findings highlight the potential benefits of adopting high ΔT chilled water designs in office buildings. The results not only demonstrate cost-effectiveness but also underscore the importance of energy efficiency and sustainability in building design and operation. The outcomes of this study contribute to the existing body of knowledge in the field and provide valuable insights for building professionals and stakeholders seeking optimal cooling system solutions. By embracing high delta T designs, practitioners can achieve significant benefits in terms of reduced capital expenditures and ongoing energy consumption, leading to a more sustainable and economically viable built environment.
dc.identifier.conferenceMoratuwa Engineering Research Conference 2024
dc.identifier.departmentEngineering Research Unit, University of Moratuwa
dc.identifier.emailjosephai.20@uom.lk
dc.identifier.emailanusha@uom.lk
dc.identifier.facultyEngineering
dc.identifier.isbn979-8-3315-2904-8
dc.identifier.pgnospp. 169-174
dc.identifier.placeMoratuwa, Sri Lanka
dc.identifier.proceedingProceedings of Moratuwa Engineering Research Conference 2024
dc.identifier.urihttps://dl.lib.uom.lk/handle/123/25423
dc.language.isoen
dc.publisherIEEE
dc.subjectENERGY EFFICIENCY
dc.subjectHIGH DELTA T
dc.subjectCHILLED WATER
dc.subjectOFFICE BUILDING
dc.subjectTROPICAL COUNTRY
dc.titlePotential energy saving with high ΔT chilled water designs compared to the conventional low ΔT designs for office buildings in hot and humid climates
dc.typeConference-Full-text

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
1571018709.pdf
Size:
1.43 MB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description:

Collections