Consideration of damages of a floating roof-type oil storage tank due to thermal stress

dc.contributor.authorHirokawa, Y
dc.contributor.authorYamada, M
dc.contributor.authorNishi, H
dc.contributor.authorZama, S
dc.contributor.authorHatayama, K
dc.date.accessioned2013-11-26T17:58:15Z
dc.date.available2013-11-26T17:58:15Z
dc.date.issued2013-11-26
dc.description.abstractSeveral cracks were found on some actual floating roofs of the crude oil tanks in a southern Japan refinery. It was assumed that one of the causes is due to thermal stress during the day. In order to figure out whether the thermal stress could cause damage on the floating roof, strain and temperature were measured on the actual floating roof by using optical fiber gauges. Furthermore, thermal stress analysis and fracture possibility estimation were also carried out as additional analysis. As a result, thermal stress on the floating roof turned to be relatively small and could not cause the initial crack. However, the temperature fluctuation in a day could affect the crack propagationen_US
dc.identifier.conferenceInternational Conference on Sustainable Built Environment (ICSBE-2010)en_US
dc.identifier.pgnos450-456 pp.en_US
dc.identifier.placeKandyen_US
dc.identifier.urihttp://dl.lib.mrt.ac.lk/handle/123/9433
dc.identifier.year2010en_US
dc.language.isoenen_US
dc.subjectOil storage tanken_US
dc.subjectFloating roofen_US
dc.subjectMeasurementen_US
dc.subjectOptical fiber gaugeen_US
dc.subjectThermal stress analysisen_US
dc.subjectFEMen_US
dc.subjectFracture probabilityen_US
dc.subjectCracken_US
dc.titleConsideration of damages of a floating roof-type oil storage tank due to thermal stressen_US
dc.typeConference-Full-texten_US

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
59.pdf
Size:
537.71 KB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description: